2 Cores Power Cable (XLPE Insulated) Characteristics
Cross-sectional Area (mm²) | No.&diameter of wire (N/mm) | Average overall diameter (mm) | Reference weight (kg/km) | Conductor Resistance (Ω/km) 20ºC Max |
2x1.5 | 1/1.38 | 12.0 | 180 | 12.1 |
2x2.5 | 1/1.76 | 12.8 | 217 | 7.41 |
2x4.0 | 7/0.85 | 14.4 | 286 | 4.61 |
2x6.0 | 7/1.04 | 15.4 | 349 | 3.08 |
2x10 | 7/1.35 | 17.4 | 482 | 1.83 |
2x16 | 7/1.7 | 19.4 | 652 | 1.15 |
2x25 | 10/1.83 | 17.2 | 663 | 0.727 |
2x35 | 14/1.83 | 18.8 | 868 | 0.524 |
2x50 | 19/1.83 | 21.1 | 1153 | 0.387 |
2x70 | 27/1.83 | 23.8 | 1568 | 0.268 |
2x95 | 37/1.83 | 26.1 | 2067 | 0.193 |
2x120 | 30/2.32 | 28.8 | 2613 | 0.153 |
2x150 | 37/2.32 | 32.1 | 3185 | 0.124 |
2x185 | 37/2.52 | 35.0 | 3860 | 0.0991 |
2x240 | 48/2.52 | 38.9 | 4930 | 0.0754 |
2x300 | 61/2.52 | 43.3 | 6166 | 0.0601 |
2x400 | 61/2.95 | 48.5 | 8330 | 0.0470 |
Description Of 2 Cores Power Cable (XLPE Insulated)
Rated Temperature: 90℃
Rated Voltage: 600/1000V
Reference Standard: IEC60502
Conductor: Shaped and circular stranded copper conductors
Insulated: Insulated with cross-link polyethylene compound
PVC bedded
Flame retardant PVC sheathed overall
Application Of 2 Cores Power Cable (XLPE Insulated)
For fixed installation of the transmission and distribution systems, tunnels and pipelines and other occasions
For situation not suppose to bear the external mechanical force