Single Core Power Cable (PVC Insulated) Parameter
Cross-sectional Area (mm2) | No.&diameter of wire (N/mm) | Average overall diameter (mm) | Reference weight (kg/km) | Conductor Resistance (Ω/km) 20℃ Max |
1.5 | 1/1.38 | 5.8 | 28 | 12.1 |
2.5 | 1/1.76 | 6.2 | 31 | 7.41 |
4.0 | 7/0.85 | 7.4 | 38 | 4.61 |
6.0 | 7/1.04 | 7.9 | 42 | 3.08 |
10 | 7/1.35 | 8.9 | 48 | 1.83 |
16 | 7/1.7 | 9.4 | 55 | 1.15 |
25 | 7/2.14 | 11.4 | 66 | 0.727 |
35 | 19/1.53 | 12.9 | 74 | 0.524 |
50 | 19/1.78 | 14.5 | 84 | 0.387 |
70 | 19/2.14 | 16.5 | 103 | 0.268 |
95 | 19/2.52 | 19 | 129 | 0.193 |
120 | 37/2.03 | 20.8 | 151 | 0.153 |
150 | 37/2.25 | 22.8 | 167 | 0.124 |
185 | 37/2.52 | 25.3 | 197 | 0.0991 |
240 | 61/2.25 | 28.5 | 235 | 0.0754 |
300 | 61/2.52 | 31.5 | 275 | 0.0601 |
400 | 91/2.36 | 35.4 | 326 | 0.0470 |
500 | 91/2.65 | 39.2 | 399 | 0.0366 |
Description of Single Core Power Cable (PVC Insulated)
Rated Temperature: 70℃
Rated Voltage: 600/1000V
Reference Standard: GB/T12706, IEC60502, BS6346
Model: VV
Shaped stranded copper conductors
Flame retardant insulated with PVC compound
PVC bedded
Flame retardant PVC sheathed overall
Application of Single Core Power Cable (PVC Insulated)
• For fixed installation of the transmission and distribution systems, tunnels and pipelines and other occasions.
• For situation not suppose to bear external mechanical force.